Interfaces
Vocia CI-1
Vocia control interface for use between fire alarm and Vocia LSI-16 or Vocia LSI-16e (EN54-16 certified).
Key features
- High reliability switches for Local Sounder Silence, System Test, and System Fault Reset
- High level sounder for Fault/Alarm warning
- Dual 24 volt DC power summing with power loss fault connection
- Provides terminating resistors for Alarm and Fault Inputs
- Provides terminating resistors for any unused monitored outputs
- Current limited reference voltage output
- Rack mountable (1RU)
- EN 54-16 certified, EN 60849 and AS 60849 verified, CE marked, and RoHS compliant
- 5-year warranty
- Compliant with the US Trade Agreement Act (TAA)
The CI-1 Control Interface is a device that serves as a companion product to the Vocia LSI-16 and LSI-16e Life Safety Interfaces. The CI-1 requires an LSI-16 or LSI-16e for operation. Once the required interconnections have been established, the CI-1 will operate with the LSI-16 and LSI-16e to provide the necessary life safety functionality. The CI-1 also facilitates the necessary connections to the LSI-16 and LSI-16e for EN 54-16 standards compliance.
The Vocia CI-1 complies with the United States Trade Agreement Act (TAA), allowing it to be included in GSA Schedule contractors’ sales bids for the U.S. federal government.
| General | |
|---|---|
| Height | 1.75 inches (44.5 mm) |
| Width | 19.0 inches (483 mm) |
| Depth | 10.0 inches (254 mm) |
| Weight | 6.4 lbs (2.8 kg) |
| Power | |
| Power | Dual 24V DC, 15W each |
| Power Input | ALARM INPUTS: Assertion: Transition from 0V to 12-24V FAULT INPUTS: Assertion: Transition from +V to 0V Maximum pull-up resistor: 2.2kΩ |
| Power Output | OUTPUTS: Assertion: Low Pull-up Load: max 2.2kΩ Maximum External Supply: 35V Maximum Continuous Current 350mA Current Limit: 800mA |
| Certified Solutions | |
| TAA Compliant | TAA Compliant |
| Certified Solutions | TAA Compliant |
| Compliance | |
| Certifications | EN 54-16 certified CE marked (Europe) RINA (Italy) RoHS Directive (Europe) EN 60849, AS 60849 verified |
| Environmental | |
| Ambient Operating Temperature Range | 32-113° F (0 – 45° C) |
| Humidity | 0 – 100% non-condensing |
| Altitude | 0-10,000 Feet (0-3000 Meters) MSL |