Interfaces
Vocia LSI-16e
An enhanced life-safety interface that connects Vocia systems to fire alarm and emergency control equipment, delivering certified reliability, redundant networking, and intelligent monitoring for voice evacuation and emergency communication systems.
Key features
- Integrate seamlessly with life-safety systems — parallel I/O ports and monitored emergency inputs provide direct connectivity to fire and emergency equipment.
- Maintain compliance and readiness — EN 54-16 certified and EN/AS 60849 verified for use in regulated voice alarm installations.
- Ensure operational resilience — redundant power inputs (24VDC battery + PoE) and dual network ports support fault-tolerant operation.
- Scale to complex emergency workflows — up to 4 discrete emergency inputs and 16 programmable general-purpose inputs enable extensive control logic.
- Monitor system integrity — short-to-ground and open-circuit detection ensures line faults are identified immediately.
- Support large system integrations — up to 500 virtual inputs via RS-232 or Ethernet enable high-volume command and control.
- Simplify installation and configuration — local configuration storage, rotary ID switches, and status LEDs streamline setup and diagnostics.
- Invest with confidence — the LSI-16e is CE marked, RoHS compliant, and backed by a 5-year warranty.
The Vocia LSI-16e is an enhanced life-safety interface module designed to bridge Vocia paging and evacuation systems with fire alarm and emergency control systems. Its comprehensive set of monitored I/O, redundant power options, and certified compliance make it a critical component for mission-critical voice alarm applications in airports, campuses, industrial facilities, transportation hubs, and large public venues.
The LSI-16e supports up to three power sources, including a standards-compliant, battery-backed 24V DC supply for life-safety installations, as well as PoE via either of its two network ports. This redundancy ensures continuous operation even during power anomalies.
Equipped with 8 monitored I/O ports and 8 control inputs, plus up to 4 discrete emergency inputs, the device provides extensive interfacing capabilities for fire alarm triggers, evacuation mode changes, zone resets, and silencing functions. An additional 16 general-purpose inputs can be configured for TTL, high-range, or monitored high-range operation, allowing detailed supervision and fault detection such as open circuits or shorts to ground.
For larger systems, the LSI-16e supports up to 500 virtual inputs over RS-232 or Ethernet, enabling advanced integration with third-party control platforms. Local storage of configuration data and rotary ID switches simplify commissioning, while front-panel LEDs provide immediate status visibility. Rack-mountable in 1RU, the unit installs easily in equipment rooms or network racks.
Fully EN 54-16 certified, verified to EN 60849 and AS 60849, and fully RoHS compliant, the Vocia LSI-16e provides a robust, standards-aligned solution for life-safety paging systems. Backed by a 5-year warranty, it delivers the durability and reliability required for regulated emergency communications.
Compliant with the US Trade Agreement Act (TAA)
| General | |
|---|---|
| Height | 1.75 inches (44.5 mm) |
| Width | 19.0 inches (483 mm) |
| Depth | 10.0 inches (254 mm) |
| Weight | 6.4 lbs (2.9 kg) |
| Power | |
| Power | Main: 24V DC 15W PoE: 802.3af Class 3 |
| Certified Solutions | |
| TAA Compliant | TAA Compliant |
| Certified Solutions | TAA Compliant |
| Compliance | |
| Certifications | EN 54-16 certified FCC Part 15B (USA) CE marked (Europe) RoHS Directive (Europe) RINA (Italy) EN 60849, AS 60849 verified |
| Control | |
| RS-232 | PORT: Type: DTE Baud Rate: 57600 |
| Connectivity | RJ-45 with shielded Ethernet (CAT5, CAT5e, CAT6 or CAT7 |
| Environmental | |
| Ambient Operating Temperature Range | 23-104° F (-5 – 40° C) |
| Humidity | 0 – 95% non-condensing |
| Altitude | 0-10,000 Feet (0-3000 Meters) MSL |
| Audio | |
| Input Type | CONTROL INPUYS: Number: Eight Type: Opto Isolator LED Cathode presented at input – pull low to enable Sink Current: Min: 1mA Max: 6mA Maximum Terminal Voltage: 24V Isolation: 3kV GENERALPURPOSE INPUTS: Number: 16 High Range Logic Low: 0-11VDC High Range Logic High: 12-30VDC High Range Hysteresis: 1V ± 20% TTL Logic Low: 0-0.8V TTL Logic High: 2-5V TTL Hysteresis: 1V ± 20% Input Transient Protection: ± 8kV peak Input Isolation: 500V RMS (isolation from LSI-16) |